QUESTION
Trying to read data from the energy meter. The code suppose to read voltage data and return but it's some random numbers are showing. Where am I making mistake in the code? Meter is conzerv EM6436 Energy Meter. Tried:- 1) converting data in uint16_t fail 2) Reading different other registers fail 3) The energy meter showing correct data on modscan. Energy Meter register Link
...ANSWER
Answered 2021-Mar-24 at 06:49As Bosz suggested in the comments above, the first thing you need to do is read two Modbus registers instead of 1. So change:
QUESTION
I have been trying to acquire electrical parameters from my energy meter using Arduino through Modbus communication. But my code fails to get the data from the meter. In this code, I'm trying to get the phase voltage value from the energy meter whose register address is 12.
...ANSWER
Answered 2021-Mar-19 at 16:22You are using the wrong Modbus function. You should be using function 0x03 readHoldingRegisters
(note the 0x03 at the beginning of the frame on the bottom side of the page).
Just change this line:
QUESTION
I am new to coding and i want to connect my pi to Schneider pm 1200 to get values of holding registers. and when i executed it, i got many errors related to exception.
How to write register? I am trying to use writeSingleRegister method ,but I cant's get it's register type error.
I am using j2mod
jar file
This is the code
...ANSWER
Answered 2020-Jun-07 at 13:25At runtime, the code executed for a Java program starts out in "class files", stored by the compiler in files with a ".class" extension. These files are often packaged in groups in "jar files", and the Java runtime can find the classes in the jar files while it's running.
Your error indicates that the runtime cannot find the class indicated. The java.io.SerialPortEventListener class appears to be available in the jar file rxtx-2.1.7.jar. You can download that (search for its reliable source) and copy it to the target machine. You'll then need to read up on what a classpath is; you can set a classpath in an environment variable or with a parameter passed to the "java" command at runtime. Either way, the runtime can find the class in that jar file when you run your program.
I've touched on a handful of concepts here; am sorry it isn't a real simple do 1-2-3 kind of answer, but you'll need to understand jar files and the classpath as you code more.
QUESTION
I am trying to get a simple Modbus running and I am getting trouble with the sequense of commands.
I have figured first, that I can't run multiple functions in a function. If I do this, then it looks like a connection was made, but it fails. If I create 2 buttons ("Connect", "Read") and click first connect and then read, then the connection was succesfully and i am able to read the response.
So how can I change the code, so that it will connect to a TCP Modbus, read some data and then close the connection with one function/button?
This is an example of my code:
In file modbusmaster.hpp:
...ANSWER
Answered 2020-Aug-06 at 22:24Many people fail to realise, that communications take time. So, in your case, you open the device and immediatelly initiate a read request, which fails, because the device is not open yet (because it takes time, as everithing else).
SolutionIn a GUI application, it is probably the best, when the code reacts to events, instead of trying to execute everything lineary. This is where signals and slots come into play.
Consider the following workflow:
when you create the QModbusDevice
, you also connect its signals (e.g. stateChanged
and errorOccurred
) to slots in your code (e.g. MainWindow::onModbusStateChanged
, or MainWindow::onModbusErrorOccurred
). Those should be considered as callback functions, which are executed when the corresponding event occurs: the connection state changes, the data is received, the data is sent, an error occurs.
In this manner you would know exactly when to do what.
ExampleHere is an example code I have prepared for you to show you how the problem could be approached:
in MainWindow.h
QUESTION
I have worked on metering the modbus data and i did it for 16 bit and 32 bit data. but now i have a requirement of 64 bit data.
...ANSWER
Answered 2019-Jul-23 at 09:31You need to be careful with your data types.
First thing to consider is that one Modbus register stores 16 bit.
So two registers should be 32 bit and 4 registers 64 bit.
With that in mind, you need to review the manual of your device and see the width of each data word, which is the number of registers you need to read.
QUESTION
I am working on mod-bus registers. I am new to this field so i am facing some of the issues. I have get the data in an array from the mod-bus and it is displaying my values into int but i want the data in real data type. Waiting for your kind response. P.S: kindly ignore my mistakes
...ANSWER
Answered 2019-Jun-28 at 06:26It depends on how your data is represented. In Modbus you need two registers to store a float. Then you need to check on the manual of your device the endianness of these registers and the order of the bits within.
If you read registers two at a time then you can use the helper function provided with phpModbus:
QUESTION
I'm writing a Modbus client program using Qt5 and the QModbusTcpClient
class. Here the code I'm using for open a connection and read something:
ANSWER
Answered 2018-Nov-22 at 12:44It depends on type of an equipment, you are working with. You just have to follow the logic, described in equipment mans for this particular exception.
In general there is no special 'Program Complete' event. That means, as it is written for 0x5 - "Specialized use in conjunction with programming commands.". So you just have to poll (read) some flag from your device meaning the internal process in device, which caused this exception, is complete.
Just as an example, I've met with such exception in relay protection device, which issued it when it has been in a process of writing a disturbance record. I had just to check for that record readiness in some time.
Community Discussions, Code Snippets contain sources that include Stack Exchange Network
Vulnerabilities
No vulnerabilities reported
Install ModbusMaster
Support
Reuse Trending Solutions
Find, review, and download reusable Libraries, Code Snippets, Cloud APIs from over 650 million Knowledge Items
Find more librariesStay Updated
Subscribe to our newsletter for trending solutions and developer bootcamps
Share this Page