jlibmodbus | Modbus protocol v1.1b in java language | TCP library
kandi X-RAY | jlibmodbus Summary
kandi X-RAY | jlibmodbus Summary
The MODBUS protocol implementation in pure java.
Support
Quality
Security
License
Reuse
Top functions reviewed by kandi - BETA
- Starts the program
- Tries to select a supported connector factory
- Get the SerialPortAbstractFactory
- Reads a single byte from the buffer
- Read a single byte from the loopback
- Read a number of bytes from the wire
- Reads bytes from the wire
- Start the slave
- Open the modbus
- Starts the slave
- Clear counters and diagnostic registers
- Returns true if the sub - function is the same
- This function creates a new ModbusRequest instance
- Closes the server
- Main entry point
- Main loop of the server
- Reads data from a file
- This method returns the response of the comms response
- Writes a response to the index
- Main method for running a slave
- Process the Constraint Level
- Creates a modbus master
- Starts the slave
- The main method
- Creates a serial port
- Reads a response from a file
jlibmodbus Key Features
jlibmodbus Examples and Code Snippets
Community Discussions
Trending Discussions on jlibmodbus
QUESTION
My use case is as follows. I'm developing a large spring based application and we are using spring boot logging throughout. However, for various reasons I need to use a third-party library that uses java.util.Logger in its internals. This causes the two separate loggers to both send their output to our console.
I've found many examples on how to configure spring boot logging to use java logging as its output, but I haven't been able to determine how to go the other way.
The library in question - JLibModbus - includes API access to set it's logging level or to turn it off, but I don't see any way to actually tell it to use a different logger. Presumably this should be possible. I'm hoping that someone else has already done this.
(Actually I'm working in Kotlin, not Java, but any answer that works in one I should be able to convert to the other.)
...ANSWER
Answered 2019-Apr-03 at 17:17If I understand you correctly, you want to configure the logging of a lib which uses Java Util Logging.
Spring Boot comes already with a managed dependency which helps you to fix your issue.
Please add or verify that you've already added the JUL to SLF4J bridge:
QUESTION
I am using jlibmodbus library to read slave registers. I am able to read registers from 0 to 125 but if I try to read registers value 126 or greater the I get error saying error in start offset.
I have around 500 registers, how do I read all in one go using read holding registers.
...ANSWER
Answered 2017-Dec-12 at 09:56A Modbus read register response (functions Read Input Register or Read Holding Register) has space for 125 registers.
You need to issue four requests to read 500 registers. In each request you specify the start address:
- request 1: start address=0, number of registers=125
- request 2: start address=125, number of registers=125
- request 3: start address=250, number of registers=125
- request 4: start address=375, number of registers=125
The addresses used here are fictional, you need to check your device's Modbus mapping to get the correct ones.
Community Discussions, Code Snippets contain sources that include Stack Exchange Network
Vulnerabilities
No vulnerabilities reported
Install jlibmodbus
You can use jlibmodbus like any standard Java library. Please include the the jar files in your classpath. You can also use any IDE and you can run and debug the jlibmodbus component as you would do with any other Java program. Best practice is to use a build tool that supports dependency management such as Maven or Gradle. For Maven installation, please refer maven.apache.org. For Gradle installation, please refer gradle.org .